NA2XBY Cable XLPE Insulated STA Cable AL/XLPE/STA/PVC

AL/XLPE/STA/PVC XLPE Insulated Cable

NA2XBY cable is suitable for AC 50Hz power and distribution lines with rated voltage of 600/1000V, which can be used   

· in fixed industrial power applications

· Underground tunnels

· in power and switching stations

· local energy distributions

· industrial plants

Using steel tape armouring offers great mechanical protection, making it rigid with a large radius in installation indoors and outdoors.

For any more information or advice please contact the office on 0086-13229065196(WhatsApp/WeChat)

Share:

Details

600/1000V,XLPE Insulated Cables, With steel armoured,PVC Sheath

0.6/1 KV AL/XPLE/STA/PVC cable plays a vital role in low-voltage power transmission and distribution, widely applied in building,industrial, and infrastructure settings to ensure the reliability and safety of power systems. This Power Cable with stranded compacted copper conductor is composed of aluminum conductor (AL), cross-linked polyethylene insulation (XPLE), steel tape armoring for mechanical protection and a polyvinyl chloride sheath (PVC). For fixed installation in interiors,outdoor installation,in soil,in water and concrete,if no posterior mechanical damage is to be expected.

Construction

NA2XBY Cable XLPE Insulated STA Cable AL/XLPE/STA/PVC

Description: NA2XBY, XLPE Insulated Aluminum Power Cable   

Conductors:Class 1 or Class 2 of plain aluminum,or of Class 5 of plain aluminum in accordance with IEC 60228.

Insulation:Cross-linked polyethylene XLPE

Insulation Colour:Natural or as required

Filler:  Non-hygroscopic Material

Inner Sheath: Polyvinyl Chloride PVC

Outer Sheath:Extruded Polyvinyl Chloride PVC&Polyethylene PE&LSZH

Colour of Sheath:  Black

Voltage Rating (Uo/U):600/1000V   

Test Voltage: 3.5kV for 5 minutes

Physical Properties

Maximal operating conductor Temperature: up to 70℃(PVC insulation); up to 90(XLPE insulation)

Operating Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)

Short Circuit Temperature(5 seconds maximum duration): 140-160℃(PVC insulation);250℃(XLPE insulation)

Technical Data

0.6/1kV-2 core aluminum conductor XLPE insulated steel tape armored PVC sheathed power cable
Nominal cross sectional areaInsulation thicknessNon-magnetic steel tape thickness Sheath thicknessApproximate outer diameterApprox.
weight
Max.D.C resistance of conductor(20℃)Current carrying capacity 
mm2mmmmmmmmkg/kmΩ/kmIn Air(A)In Ground(A)
2X2.50.70.21.813.4236 12.1-23 
2X40.70.21.814.3269 7.41-30 
2X60.70.21.815.3307 4.61-38 
2X100.70.21.817.8397 3.0850 47 
2X160.70.21.820.0493 1.9164 62 
2X250.90.21.823.3643 1.286 78 
2X350.90.21.824.6738 0.868105 94 
2X501.00.21.827.2896 0.641125 110 
2X701.10.21.931.41164 0.443165 135 
2X951.10.22.035.51480 0.32200 160 
2X1201.20.52.240.22164 0.253235 185 
2X1501.40.52.344.22572 0.206270 205 
2X1851.60.52.548.93089 0.164310 235 









0.6/1kV-3 core aluminum conductor XLPE insulated steel tape armored PVC sheathed power cable
Nominal cross sectional areaInsulation thicknessNon-magnetic steel tape thickness Sheath thicknessApproximate outer diameterApprox.
weight
Max.D.C resistance of conductor(20℃)Current carrying capacity 
mm2mmmmmmmmkg/kmΩ/kmIn Air(A)In Ground(A)
3X2.50.70.21.813.9257 12.1-23 
3X40.70.21.814.8296 7.41-30 
3X60.70.21.816.0342 4.61-38 
3X100.70.21.818.6447 3.0850 47 
3X160.90.21.821.0563 1.9164 62 
3X250.90.21.824.6744 1.286 78 
3X350.90.21.826.0869 0.868105 94 
3X501.00.21.928.91074 0.641125 110 
3X701.10.22.033.91443 0.443165 135 
3X951.10.52.239.02183 0.32200 160 
3X1201.20.52.342.72593 0.253235 185 
3X1501.40.52.447.53155 0.206270 205 
3X1851.60.52.652.13743 0.164310 235 
3X2401.70.52.858.34641 0.125365 260 
3X3001.80.52.963.65508 0.1420 290 









0.6/1kV-4 core aluminum conductor XLPE insulated steel tape armored PVC sheathed power cable
Nominal cross sectional areaInsulation thicknessNon-magnetic steel tape thickness Sheath thicknessApproximate outer diameterApprox.
weight
Max.D.C resistance of conductor(20℃)Current carrying capacity 
mm2mmmmmmmmkg/kmΩ/kmIn Air(A)In Ground(A)
4X2.50.70.21.814.7288 12.1-23 
4X40.70.21.815.8334 7.41-30 
4X60.70.21.817.0384 4.61-38 
4X100.70.21.820.0509 3.0850 47 
4X160.90.21.822.7649 1.9164 62 
4X250.90.21.826.7880 1.286 78 
4X350.90.21.828.31040 0.868105 94 
4X501.00.22.132.01365 0.641125 110 
4X701.10.52.138.52138 0.443165 135 
4X951.10.52.342.92638 0.32200 160 
4X1201.20.52.447.43202 0.253235 185 
4X1501.40.52.652.33847 0.206270 205 
4X1851.60.52.757.54585 0.164310 235 
4X2401.70.53.064.35709 0.125365 260 
4X3001.80.53.170.36805 0.1420 290 









0.6/1kV-5 core aluminum conductor XLPE insulated steel tape armored PVC sheathed power cable
Nominal cross sectional areaInsulation thicknessNon-magnetic steel tape thickness Sheath thicknessApproximate outer diameterApprox.
weight
Max.D.C resistance of conductor(20℃)Current carrying capacity 
mm2mmmmmmmmkg/kmΩ/kmIn Air(A)In Ground(A)
5X2.50.70.21.815.6321 12.1-23 
5X40.70.21.816.8376 7.41-30 
5X60.70.21.818.2443 4.61-38 
5X100.70.21.821.6592 3.0850 47 
5X160.70.21.824.6763 1.9164 62 
5X250.90.21.829.01029 1.286 78 
5X350.90.21.931.01236 0.868105 94 
5X501.00.22.135.71616 0.641125 110 
5X701.10.52.342.42528 0.443165 135 
5X951.10.52.447.23172 0.32200 160 
5X1201.20.52.651.83801 0.253235 185 
5X1501.40.52.757.64604 0.206270 205 
5X1851.60.52.963.85574 0.164310 235 
5X2401.70.53.270.76859 0.125365 260 
5X3001.80.53.478.08305 0.1420 290